Monday, November 15, 2010

Cheap and Cheerful Heat Loss Calculation, And The Winner Is:

After reviewing the rather complex calculations for determining heat loss, which involve converting heat content of a cubic metre of natural gas to mJ/hour, then to kW, and back to BTU's, I decided if I can find the heat content in BTU of one cubic metre of natural gas, I can simplify the calculation considerably. From a variety of sources, natural gas has a heat content of 36,000 BTU / m3:

Take your total gas consumed for a four month period from November to February, multiply by your furnaces efficiency rating (GFUE%) and divide the volume by 2880 (120 days by 24 hours)

Multiply this by a factor of 2.4, which compensates for actual average HDD for the period to maximum HDD assuming a coldest day of -35 (I used 6360 design HDD for the period - 120 days at 53 HDD per day, versus 2680 actual average HDD from Environment Canada)

Finally, multiply this by 36,000, the approximate BTU energy contained in 1 m3 of natural gas, and the result is the appropriate sized furnace for your house (one that will work non-stop when the outside temp is -35 Celsius):

2490m3 * 0.92% / 2880 HDD * 2.4 HDD * 36000 BTU/m3 = 68,724 BTU

So it looks like the furnace of choice will be 90,000 BTU, oversized just enough to fill demand on the few days that may drop below the -35 design temperature, and if down the road we wish to heat the sunroom in the winter, among other things.

It seems the winner is Dave Davies from Stratford, who (seem to at least) have a fair and reasonable price strategy, a no nonsense approach to installations (they always install a condensate pump to a drain, rather than a hose on the floor). The furnace will be an Elite Series Lennox G61V High efficiency, two-stage with variable speed DC blower motor. Not particularly pretty, but hey, it's a furnace. And with a stroke of good luck, they will be installing a Honeywell Prestige HD 7-day fully programmable setback thermostat, with remote control.

Tuesday, November 9, 2010

Furnace Sizing: Heat Loss Calculations

Since I am of the opinion that our broken down hunk of junk furnace is grossly oversized for the heating requirements of the house, I decided to do a heat loss calculation to do things properly. The existing furnace is a 130,000 BTU 92% efficiency, which I really think is in the order of half again too big, and that something like 90,000 BTU should have no issues keeping the house warm.

I found the CMHC website which has a fantastic article on replacing a furnace, including a detailed method of doing a heat loss calculation based on your fuel bills.


The only other information needed is data on heating degree days for the period you are planning to calculate, which are available at these two sites. The first link will have you search for a local weather station, and provides historical 30 year averages for the station selected. The second link provides a Canada wide average for each of the last ten years. Specific HDD values vary by location, and you should try to get both localized data, and compare this with the Canadian data, especially if you live in places that are warmer (Victoria BC) or colder (Fort McMurray AB) than the Canadian average.



Looking at our Union Gas bill covering November 2008 through February 2009 (actual consumption from Oct 21 2008 to Feb 17 2009), I then simply cut and paste the calculation portion of the text from the CMHC site, and went through adding my own numbers below:


Total gas consumption from December to March = 2620 m3

Estimating 5% of gas is used for hot water, gas consumption during the period for heating = 2620 * 0.95 = 2490 m3

Heating degree days for that period (from Environment Canada) = 2680 HDD

Heating consumption by degree day = 2490 m3/ 2680 HDD = 0.929 m3/HDD

Heating consumption (difference of -35 coldest, from 18 ambient) at 53 HDD/day = (53 HDD/day)(0.929 m3/HDD) = 49.2 m3/day

Where gas has an energy content of 37.5 MJ/m3, and the existing furnace has an efficiency of 92 per cent, then:

Heat loss at 53 HDD/day = (49.2 m3/day) (37.5 MJ/m3)(0.92) = 1697 MJ/day or (divide by 24) 70.7 MJ/h

According to the energy content of electricity, 3.6 MJ/h = 1 kW, then 70.7 MJ/h = 19.6 kW

This heat loss would require a furnace that produces an output of 19.6 kW or about 66,900 Btu/h (1 kW is approximately 3,412 Btu/h).

If we allow the CAN/CSA F280 permissible oversizing of 40 per cent, then the proper furnace sizing would be (1.4)(20,100 Btu/h) = approximately 93700 Btu/h.


The determination of the correct furnace size for a house is NOT an exact science. Ideally the furnace size that is most efficient for any house is the size that effectivly runs close to 'flat out' only on the absolute coldest day of the year. If it is too small, it will not be able to keep the house warm enough, and if too large, it has an easy time heating during extreme cold, and becomes less efficient in mild weather.